A broad-range measuring device allows for use of the test instrument in all alternating and 3-phase electrical systems with voltages from 65 to 500 V and frequencies of 15.4 to 420 Hz.
- Loop and line impedance measurement
- Measurement of insulation resistance using nominal voltage, with variable or rising test voltage
- Low-resistance measurement
- Earth resistance measurement
- Standing-surface insulation measurement
- Universal connector system
- Measurement of contact voltage without tripping the RCCB.
Contact voltage is measured with reference to nominal residual current using 1/3 of the nominal residual current value. - Tripping test with nominal residual current, tripping time measurement
Special testing for systems and RCCBs
- Testing of equipment and RCCBs with rising residual current including indication of tripping current and contact voltage at the moment the RCCB is tripped
- Testing of RCCBs with: ½ × IΔN, 1× IΔN, 2× IΔN, 5× IΔN
- Testing of RCCBs which are suitable for pulsating residual direct current; testing is conducted with positive or negative half-waves.
- Testing of RCCBs with adjustable residual current for determining contact voltage
Testing for special RCDs
- Selective S, SRCDs, PRCDs (Schukomat, Sidos and others), types G/R, AC, A and B
Additional Functions as Compared with the PROFITEST MTECH
Testing of insulation monitoring devices (IMDs)
Insulation monitors are used in power supplies for which a single-pole earth fault may not result in failure of the power supply, for example in operating rooms or photovoltaic systems.
Testing of residual current monitoring devices (RCMs)
RCMs (residual current monitors) monitor residual current in electrical systems and display it continuously. As is also the case with residual current devices, external switching devices can be controlled in order to shut down supply power in the event that a specified residual current value is exceeded.
Intelligent ramp
The advantage of this measuring function in contrast to individual measurement of IN and tA is the simultaneous measurement of breaking time and breaking current by means of a test current which is increased in steps, during which the RCD is tripped only once.
Earth resistance measurement
- Earth resistance RE (mains operation) I/U measuring method (2/3-wire measuring method via measuring adapter)
- Earth resistance RE (battery operation) 3 or 4-wire measuring method via PRO-RE adapter
- Soil resistivity (battery operation) 4-wire measuring method via PRO-RE adapter
- Selective earth resistance (mains operation) with 2-pole adapter, probe, earth electrode and current clamp sensor (3-wire measuring method)
- Selective earth resistance RE (battery operation) with probe, earth electrode and current clamp sensor (4-wire measuring method via PRO-RE adapter and current clamp sensor)
- Earth loop resistance (battery operation)with 2 clamps (current clamp sensor direct and current clamp transformer via PRO-RE/2 adapter)
Leakage current measurement with PRO-AB adapter
Measurement of continuous leakage and patient auxiliary current per IEC 62353 (VDE 0750, part 1) / IEC 601-1 / EN 60 601-1:2006 (Medical electrical equipment – General requirements for basic safety) is possible with the help of the PRO-AB leakage current measuring adapter used as an accessory with the test instrument.
Determining residual voltage / detecting mains fluctuations
The EN 60204 standard specifies that after switching supply power off, residual voltage between L and PE must drop to a value of 60 V or less within 5 seconds at all accessible, active components of a machine to which a voltage of greater that 60 V is applied during operation.
Automatic test sequence function
The use of test sequences is advisable when the same sequence of tests needs to be executed repeatedly with subsequent documentation, for example as required by the standards. Automated test sequences can be created from individual manual measurements with the help of the test sequence function.
- EASY transfer stands for direct incorporation of the Profitest Master into DDS-CAD planning software.
- Display of approved fuse types for electrical systems
- Energy meter start-up testing
- Calculation of cable lengths for common copper wire cross-sections
- Measurement of biasing, leakage and circulating current up to 1 A, as well as working current up to 150 A with the WZ12C current sensor clamp as an accessory
- Phase sequence measurement (including highest line-to-line voltage)
- Measurement of contact voltage without tripping the RCCB.
Contact voltage is measured with reference to nominal residual current using 1/3 of the nominal residual current value. - Tripping test with nominal residual current, tripping time measurement
- Interface for Bluetooth
PROFITEST | MBASE | MPRO | MTECH | MXTRA |
New | New | |||
RCD measurements | ||||
UB measurement without tripping the RCD | x | x | x | x |
Tripping time measurement | x | x | x | x |
Tripping current measurement | x | x | x | x |
Selective, SRCDs, PRCDs, type G/R | x | x | x | x |
AC/DC sensitive RCDs, types B and B+ | - | - | x | x |
Testing of insulation monitoring devices (IMDs) | - | - | - | x |
Testing of residual current monitoring devices (RCMs) | - | - | - | x |
Testing for N-PE reversal | x | x | x | x |
Loop impedance ZL-PE / ZL-N | ||||
Fuse table for systems without RCDs | x | x | x | x |
Without tripping the RCD, fuse table | - | - | x | x |
With 15 mA test current without tripping the RCD | x | x | x | x |
Earth resistance | ||||
Earth resistance RE (mains operation) I/U measuring method (2/3-wire measuring method via measuring adapter: 2-wire/2-wire + probe) |
x | x | x | x |
Earth resistance RE (battery operation) 3 or 4-wire measuring method via PRO-RE adapter |
- | x | - | x |
Soil resistivity ρE (battery operation) (4-wire measuring method via PRO-RE adapter) | - | x | - | x |
Selective earth resistance RE (mains operation) with 2-pole adapter, probe, earth electrode and current clamp sensor (3-wire measuring method) | x | x | x | x |
Selective earth resistance RE (battery operation) with probe, earth electrode and current clamp sensor (4-wire measuring method) via PRO-RE adapter and current clamp sensor) | - | x | - | x |
Earth loop resistance ρEloop (battery operation) with 2 clamps (current clamp sensor direct and current clamp transformer via PRO-RE/2 adapter) | - | x | - | x |
Equipotential bonding measurement RLO with automatic polarity reversal |
x | x | x | x |
Insulation resistance RISO with variable or rising test voltage (ramp) |
x | x | x | x |
Variable or rising test voltage | x | x | x | x |
Voltage measurement UL-N / UL-PE / UN-PE / f |
x | x | x | x |
Special measurements | ||||
Leakage current (clamp meter measurement) IL, IAMP Phase sequence Earth leakage resistance RE(ISO) Voltage drop Standing surface insulation ZST Meter start-up |
x x x x x x |
x x x x x x |
x x x x x x |
x x x x x x |
Leakage current with PRO-AB adapter | - | - | - | x |
Residual voltage test | - | - | - | x |
Intelligent ramp | - | - | - | x |
Features | ||||
Selectable user interface language | x | x | x | x |
Memory (database for up to 50,000 objects) | x | x | x | x |
Automatic test sequence function | - | x | - | x |
RS 232 port for RFID/barcode scanner | x | x | x | x |
USB port for data transmission | x | x | x | x |
Interface for Bluetooth | - | - | - | x |
ETC user software for PC | x | x | x | x |
Measuring category: CAT III 500 V / CAT IV 300 V | x | x | x | x |
DAkkS calibration | x | x | x | x |
Article number | M520M | M520N | M520o | M520P |
PROFITEST | MBASE | MPRO | MTECH | MXTRA |